SafeX110 Multi Core - LSZH 125°C - Tinned Copper Cables

Application:

Power supply in demanding applications, wiring of switchboards, control, general wiring, industrial applications and communication systems. Used where low smoke, zero halogen (LSZH) is needed and where higher current ratings are required.

Benefits

Flame Retardant

Flame resistant, low fire load and non flame propagating

Extreme Flexibility

Class 5 flexible conductor stranding

Easy to Solder Tinned copper conductors for easy adhesion

Cross-Linked

Insulation and sheath are fully cross-linked to enhance performance

Low Smoke

Reduced smoke emission in a fire situation

Low Toxicity

Reduced toxicity in a fire situation

Non-Corrosive

No corrosive gas emission in a fire situaton

High Temperature Rating

125°C temperature rating can allow for higher currents and so smaller conductor sizes may be used

Features

Up to 50% higher current ratings compared to PVC flexible cable
Reduced overall diameters compared with PVC flexible cable
Cross-linked insulation and sheath form a stronger lattice and do not melt or flow when heated
Tinned copper strands for corrosion protection
Tinned copper for high conductivity soldered connection
Class 5 conductors for extreme flexibility for those awkward to get connections
RoHS compliant to comply with European environmental requirements
LSZH to reduce hazards during a fire

Construction

Colours

2 Core – Light blue, brown
2 Core + E – Light blue, brown, green/yellow
3 Core + E – Light blue, brown, black, green/yellow
4 Core + E – Light blue, brown, black, grey, green/yellow

Conductor

Tinned annealed copper wire, class 5

Insulation

X-HF-110 (Crossed linked halogen free to 110°C)

Sheath

HFS-110-TP

Ratings

Temperature

-40°C to + 125°C

Voltage

0.6/1kV

Applicable Standards

AS/NZS1125, AS/NZS3808, AS/NZS5000.1, AS/NZS1660.5.6, IEC 60228, IEC 60332-1

*Current ratings below based on AS/NZS3008.1.1:2009 table 12, column 5 and table 15, column 5 or table 16

Products

Code Construction STRANDING No. of Strands/mm NOMINAL DIAMETER mm Current Rating Amps WEIGHT Kg/km Enquire About
24200 2C 0.75 24/0.20 8.7 7.5 90
24201 2C 1 32/0.20 9.1 23 98
24202 2C 1.5 30/0.25 9.6 28 113
24203 2C 2.5 50/0.25 10.5 38 143
24204 2C 4 56/0.30 11.6 50 186
24300 3C 1.5 30/0.25 10.0 28 135
24301 3C 2.5 50/0.25 11.0 38 176
24302 2C 4 + E2.5 56/0.30 + 50/0.25 12.3 50 235
24303 2C 6 + E2.5 84/0.30 + 50/0.25 13.8 63 312
24304 2C 10 + E4 140/0.30 + 56/0.30 16.2 88 455
24305 2C 16 + E6 224/0.30 + 84/0.30 17.7 116 643
24306 2C 25 + E6 350/0.30 + 84/0.30 22.6 154 980
24307 2C 35 + E10 494/0.30 + 140/0.30 25.2 190 1303
24400 4C 1.5 30/0.25 10.8 24 164
24401 4C 2.5 50/0.25 11.9 32 216
24402 3C 4 + E2.5 56/0.30 + 50/0.25 13.3 42 294
24403 3C 6 + E2.5 84/0.30 + 50/0.25 15.0 54 392
24404 3C 10 + E4 140/0.30 + 56/0.30 17.7 75 580
24405 3C 16 + E6 224/0.30 + 84/0.30 20.3 99 839
24406 3C 25 + E6 350/0.30 + 84/0.30 24.9 131 1267
24407 3C 35 + E10 494/0.30 + 140/0.30 28.0 162 1707
24500 4C + E 1.5 30/0.25 11.6 24 189
24501 4C + E 2.5 50/0.25 12.8 32 257
24502 4C 4 + E2.5 56/0.30 + 50/0.25 14.4 42 352
24503 4C 6 + E2.5 84/0.30 + 50/0.25 16.3 54 473
24504 4C 10 + E4 140/0.30 + 56/0.30 19.3 75 703
24505 4C 16 + E6 224/0.30 22.3 99 1027
24506 4C 25 + E6 350/0.30 + 84/0.30 27.4 131 1555
24507 4C 35 + E10 494/0.30 + 140/0.30 30.9 162 2108