SafeX125 - LSZH 125°C - Flexible Single Core Tinned Copper Cable

Application:

Wiring of switchboards, control, general wiring, instrumentation and communication systems. Used where LSZH (Low Smoke Zero Halogen) is needed and where higher current rating are required.

Benefits

Cross-Linked

Insulation is fully cross-linked to enhance performance

Low Smoke

Reduced smoke emision in a fire situation

Low Toxicity

Reduced toxicity in a fire situation

Non-Corrosive

No corrosive gas emission in a fire situaton

High Temperature Rating

125°C temperature rating allows for higher current carrying capacity

Flame Retardant

Flame retardant, low fire load and non flame propagating

Extreme Flexibility

Class 5 flexible conductor stranding

Easy to Solder Tinned copper conductors for easy adhesion

Features

Up to 50% higher current ratings compared to PVC flexible cable
Reduced overall diameters compared with PVC flexible cable
Cross-linked insulation forms a stronger structure and does not melt or flow when heated
Oxygen free tinned copper for high conductivity soldered connections and corrosion protection
RoHS compliant to comply with European environmental requirements

Construction

Colours

Red, black, blue, white, brown, grey, orange, purple,pink, yellow, green, and green/yellow. Others available upon request

Conductor

Oxygen free tinned annealed copper wire, class 5 or 6

Insulation

X-HF-110

Ratings

Temperature

-40°C to + 125°C

Voltage

0.6/1kV

Applicable Standards

AS/NZS1125, AS/NZS3808, AS/NZS5000.1, AS/NZS1660.5.6, IEC 60228, IEC 60332-1

Low Smoke Zero Halogen

Flexible Conductor

Maximum Short Circuit Temperature 250°C (Max 5s)

Flame Non-Propagation

Tinned Copper for Corrosion Resistance

Impact Resistant

Minimum Recommended Bend Radius Fixed 4 x OD

Minimum Service Temperature -40°C

Maximum Service Temperature 125°C

Abrasion Resistant

Chemical And Oil Resistant

Bambach Product Specifications

Description
SafeX110 Single Core Catalogue Download

Products

Code Conductor CSA mm² STRANDING No. of Strands/mm NOMINAL DIAMETER mm Current Rating Amps WEIGHT Kg/km Enquire About
26697 0.5 16/0.20 2.3 10 10
26698 0.75 24/0.20 2.5 16 14
26699 1 32/0.20 2.7 26 17
26700 1.5 30/0.25 3.0 32 21
26701 2.5 50/0.25 3.4 43 32
26702 4 56/0.30 4.0 57 47
26703 6 84/0.30 4.7 73 68
26704 10 140/0.30 5.8 102 109
26705 16 224/0.30 6.9 135 168
26706 25 350/0.30 8.8 178 264
26707 35 494/0.30 10.2 221 365
26708 50 684/0.30 12.6 279 509
26709 70 969/0.30 15.7 351 734
26710 95 1292/0.30 17.1 422 959
26711 120 1653/0.30 18.4 500 1197